Halogen-free rigid pipe 4422
Rigid metric installation pipe 4422 halogen-free
CND-ASSEMBLEYHELP-(W-IS-EL-F-HO)-EN20
Art.-no.
0975264020
EAN 4045989299461
Prices for customers after login
Exclusively for trade customers
Register now and access more than 125,000 products
Halogen-free. For installations in public premises and in premises with fire or explosion hazard.
- Classification code: 44221254-010 according to standard UNE-EN 61386-1.
- Material: Halogen-free thermoplastic polymer. In accordance with UNE-EN 50267/2-2 on "halogen-free material" (formerly UNE-21147/2).
- Colour: Grey RAL 7035.
- Bending resistance: Rigid pipe (in accordance with UNE-EN 61386-21).
- Non-flame propagator.
- Dielectric strength: > 2 kV (at 50 Hz).
- Insulation resistance: > 100 MΩ (at 500 V).
- Degree of protection against mechanical damage: > Z10J (impact resistance - grade 9, code IK09)
Physico-chemical features: UNE-EN 61386-21
Dimensions (metric): UNE-EN 60423
Degree of protection provided by enclosures: UNE-20324 (EN 60529)
Product information
Datasheets(X)
Outer diameter | 20 mm |
Internal diameter | 14.5 mm |
Length of rod | 3 m |
Select RAL-colour code
!! NOTE: On-screen visualisation of the colour differs from real colour shade!!